Line Post Insulator 57 Series Vertical Clamp Type and Horizontal Clamp Type
Standard: IEC60383, ANSI C29.1, ANSI C29.7
Voltage:15-45kV
Vertical clamp type line post mounted upright on crossarms and structures
Horizontal clamp type line post assemblies for ratings 15 kV through 45 kV.
Vertical clamp type line post mounted upright on cross arms and structures
1.These Horizontal Mounting Porcelain Line Post Insulators are used for flat surface mounting, having a mounting base for attaching to pole gains or bracket for mounting on concrete or steel poles and steel structures.They are rated from 25kV to 115kV.
2.They each are made up of a clamp ,a metal cap on the insulator head, a flat base, a insulator body and a stud.Clamps are for conductor sizes from 0.25″ to 2.70″. Gray color and brown color are available. Studs are also supplied according to requirement.
3.The ANSI standard No. for these Horizontal Mounting Porcelain Line Post Insulators are : 57-21,57-22,57-23,57-24,57-25 etc.
Horizontal clamp type line post assemblies for ratings 15 kV through 45 kV.
1.Clamp Top Porcelain Line Post Insulators are designed for upright mounting on cross arm or structures.They are made up of clamps , insulator body and studs and are rated from 25kV to 115kV,requiring a cantilever strength of 2800lB.
2.A metal cap, cemented to the outside of the insulator head,supports the trunion type clamp. There is a single cap screw at one end of the clamp with captive lock washers allowing easy,quick installation and removal of clamp.
3.Clamps for use with these insulators are for standard trunion type.Clamps for all conductor sizes from 0.25″ to 2.70″ in ferrous or aluminum.Gray glaze is standard for this Clamp Top Porcelain Line Post Insulators. Brown glaze is also offered when required.
4.The ANSI standard No for these Clamp top porcelain line post insulators are as follow: 57-11,57-12,57-13,57-14,57-15 etc.
ANSI CLASS |
57-11 |
57-21 |
57-12 |
57-22 |
57-13 |
57-23 |
Creepage Distance (mm) |
356 |
356 |
559 |
559 |
737 |
737 |
H – Height To Middle of Clamp Assembly |
257 |
276 |
333 |
352 |
400 |
419 |
D – Diameter |
146 |
146 |
160 |
160 |
160 |
160 |
C – Clamp Throat Width |
102 |
102 |
102 |
102 |
102 |
102 |
Dry Arcing Distance(mm) |
165 |
165 |
241 |
241 |
311 |
311 |
Cantilever Strength(kN) |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
Low Frequency Flashover Voltage-Dry(kV) |
70 |
70 |
100 |
100 |
125 |
125 |
Low Frequency Flashover Voltage-Wet(kV) |
50 |
50 |
70 |
70 |
95 |
95 |
Critical Impulse Flashover Voltage-Pos.,(kV) |
120 |
120 |
160 |
160 |
200 |
200 |
Test Voltage to Ground(kV) |
15 |
15 |
22 |
22 |
30 |
30 |
Maximum RIV at 1000KHZ(μv) |
100 |
100 |
100 |
100 |
200 |
200 |
Q:CAN YOU HELP US IMPROT AND EXPORT?
A:We will have a professional team to serve you.
Q:WHAT’S THE CERTIFICATES DO YOU HAVE?
A:We have certificates of ISO,CE, BV,SGS.
Q:WHAT’S YOUR WARRANTY PERIOD?
A:1 year in general.
Q:CAN YOU DO OEM SERVICE?
A:YES,we can.
Q:WHAT YOU LEAD TIME?
A:Our standard models are in stock ,as for big orders ,it take about 15 days.
Q:CAN YOU PROVIDE FREE SAMPLES?
A:Yes,please contact us to know the sample policy.